Toro GreenKeeper "No Watering" Icon Stuck On: Reset or Replace Controller
Icon Prevents Manual Start, Persists After Rain Sensor Off All settings work, but No Watering icon (upper right) never clears. Reset Procedure Remove 9V battery. Power off controller for 1 minute. Power on (battery sti
Irritrol RD-600 "OF7" Blinking: Rain Delay Activated for 7 Days
Meaning of OF7 Rain delay is set to 7 days (Off for 7 days). Controller will not run any programs during this period. How to Clear Set bottom switch to OFF. Press minus (-) button 7 times until display shows current ti
Irritrol SR1 Pump Start Relay Chatters After Lightning: Test Controller Output
New Rain Bird SST-1200o Controller, Pump Cycles On/Off Rapidly Pump runs 8 sec, off 5 sec, on 2–3 sec, then stops. Buzzing from SR1 relay. Controller shows zone error. Diagnosis: Isolate Pump Start Circuit Disconnect p
Richdel 446PRI Day Selection Limited: Cannot Set Specific Days, Must Replace Controller
Controller Only Supports Interval Watering (Every 1–5 Days) No day-of-week selection. Switch sets interval: 1=daily, 2=every 2 days, etc. Cannot program Tuesday/Friday only. Solution: Replace Controller Install an Irrit
Hydro Rain Blows Fuse Only in Auto on Zone 4: Transition or Wiring Issue
Strange Behavior: Fuse Blows in Auto Mode Zone 3→4 Transition, Not in Manual Suggests an issue during the automatic handoff from Zone 3 to Zone 4. Isolation Procedure Disconnect field wire from controller terminal #4.
Rain Bird ESP-6TM "Err" Flashing: Shorted Valve Solenoid or Wiring
Error Meaning Err (without number) means one or more valves are shorting the controller. Internal breaker trips to protect the board. Find the Faulty Zone Set dial to AUTO, press OFF to clear error. Manually start zone
Orbit Watermaster 57606 Drip Zone Not Working: Valve Diaphragm or Solenoid
Sprinklers Work, Drip Zone Fails on Manual and Auto Drip zone doesnt activate; sprinklers work fine. Indicates a problem with the automatic valve for the drip zone. Typical Valve Failures Diaphragm worn/torn → wont ope
Rain Bird ESP-ME Pump Runs Continuously: Controller or Relay Fault
Pump Runs Whenever Controller Has Power, Even in OFF Unplugging controller display cable stops pump. Lightning storms and surge protector trips preceded issue. Diagnosis: Test PS/MV Terminal Voltage Identify wire on PS
Nelson EZ Pro 8300 Repeats Program After Lightning: Check Seasonal Adjust, Start Times, Programs
Post-Lightning Behavior: Program Repeats Continuously Transformer and auto-resettable fuse replaced. System runs but loops program. Three Programming Checks Seasonal Adjust:100%, controller splits run time into two cyc
Toro Vision II Plus Runs Every Cycle Twice: Seasonal Adjust or Extra Start Time
Two Common Causes 100%: At 150%, a 20-min run becomes 30 min but splits into two 15-min cycles. Set to 100%. Multiple Start Times: Check all start time slots (1, 2, 3) in the active program — only one should be set. Al
Toro EXC Controller Slide Switch Failure: Replace with Irritrol Rain Dial
Symptom: Program Switch (A/B/C) Doesnt Register Correctly Display shows Program C regardless of switch position. Jiggling sometimes works for B but not A. Programming on A also appears on C. Cause: Worn/Corroded Slide S
Richdel 446PR Lightning Damage: Controller Obsolete, Replace with Irritrol Rain Dial
Controller No Longer Manufactured Richdel 446PR hasnt been made in 10+ years. Any brand controller works as replacement. Replacement Steps Label each wire as removed from old controller (1, 2, 3… and C/common). Install
Rain Bird ESP-12LX: Schedule One Zone Weekly, Others by Custom Days
Requirement: Zone 8 Once a Week, Zones 1–7 & 9–10 on Custom Days Use two programs (A and B). Setup Program A: Set run times for Zones 1–7, 9–10. Set Zone 8 run time to OFF. Program desired days and start time. Program
Rain Bird ESP-6TM Frozen Display "Er -- --": Power Cycle and Battery Removal
Symptom: Display Frozen on Error Message After resolving a prior short circuit error, the controller now shows Er -- -- and is unresponsive. Reset Procedure Remove backup battery. Disconnect AC power for 1 minute. Reco
Richdel 446PR: No Zones Work After Valve Repair — Controller Voltage Test Needed
After Replacing Diaphragm/Solenoid on Zone 2, All Zones Dead Manual bleed works (water sprays from bleed screw), but no automatic or manual operation from controller. Step-by-Step Voltage Testing Test controller output
KwikDial Battery Symbol Flashing: Internal Memory Failure
Normal vs. Fault Behavior The battery symbol should only appear at initial power-up (charging internal memory, ~30 minutes). If it persists, the internal memory circuit has failed. Troubleshooting Disconnect power for
Richdel 476PRI Disassembly: Broken Slide Switches Mean Replace Controller
Problem: Internal Levers Fell Out After Opening The designation strip fell behind the face. Removing 3 screws released 14 blue lever arms. No diagram exists for reassembly. Verdict: Controller Is Obsolete and Unrepairab
Desert Landscape Irrigation Design: Hard-Piped Drip vs. Spaghetti Tubing
Two Contractor Proposals Spaghetti tubing from manifolds on trunk line. One zone front, one back. Low-flow emitters for succulents on same zone. Hard-piped Schedule 40 PVC to each plant with self-cleaning drip heads. Tw
Hardie 2" Valve Solenoid Replacement: Irritrol Parts Compatibility
Finding the Right Solenoid Hardie was acquired by Irritrol. The 2 Hardie valves have used the same solenoid for decades. Current Irritrol valves use the identical solenoid. Solution Take the broken solenoid to any irrig
Hunter ICC "P Err" Error: Master Valve/Pump Start Solenoid or Wiring Fault
Error Meaning P Err indicates a fault on the Pump Start (PS) or Master Valve (MV) circuit. A wire is connected to the P/MV terminal. Diagnosis Disconnect wires from the master valve solenoid. Run a zone from the contro