Hunter Pro-C "P ERR" (pump error) with a 220V pump and Hunter-22 PSR indicates the pump start relay isn't closing both legs of the 220V circuit—running the pump on 110V, which trips the breaker.
The Hunter-22 PSR has two sets of contacts (for L1 and L2 of 220V). If one set is pitted, burned, or blocked by an insect, only one leg closes. The pump draws excessive current on single-phase → thermal overload/breaker trip.
Cleaning the pump disturbed debris/contacts just enough to make brief contact. Vibration/heat then reopened the faulty leg.