Richdel 446PR "FUSE" Error on All Zones

Interpreting the "FUSE" Error on a Legacy Richdel 446PR Controller

The controller displays "FUSE" on every zone attempt. The unit is 10+ years old.

What "FUSE" Means

A short circuit detected on the station output: either a bad solenoid or a shorted field wire.

Isolation Test

  1. Disconnect the field wire from terminal #1.
  2. Run zone 1. If "FUSE" still appears with the wire disconnected, the controller's output circuit is shorted—replace the controller.
  3. If the error clears, the fault is in the valve #1 solenoid or its wiring. Test each zone similarly.

Probable Cause

Since all zones show the error simultaneously, it's unlikely all solenoids failed at once. The controller's circuit board or a common wiring fault (e.g., severed common wire touching hot) is more probable. Given the controller's age, replacement is recommended.