Hunter XC Station 1 Won't Activate from Controller—Valve Works Manually

Hunter XC 6-station: Station 1 works manually at valve, not from controller. Other stations fine.

Diagnostic Sequence

  1. Activate Station 1, measure 22-26VAC at controller terminal #1 vs COM
  2. If NO voltage → controller output failed
  3. If YES voltage → check wire continuity to valve
  4. Test solenoid (20-60 Ohms)
  5. If solenoid good → diaphragm worn, replace

Resource

Valve repair: irrigationtutorials.com