Irritrol HR-6100: Program C (Zone 4) Not Working—Valve Diagnosis

Irritrol HR-6100: Program A (zones 1-3,5) works, Program C (zone 4 only) doesn't. Zone 4 is citrus trees.

Clarification

Programs contain zones. "Program C not working" = zone 4 valve not opening.

Diagnostic Sequence

  1. Activate zone 4, measure 24VAC at controller terminal #4
  2. If no voltage → controller output failed (move wire to spare terminal)
  3. If voltage present → check wire continuity to valve
  4. Test solenoid resistance (20-60 Ohms)
  5. If solenoid good → valve diaphragm stuck or debris
  6. Clean or replace valve

Water Shutoff for Single Zone?

No—each zone has independent valve. No separate water supply control per zone.