1. Home
  2. Question and Answer
  3. Houseplants
  4. Garden Articles
  5. Most Popular Plants
  6. Plant Nutrition

Hunter ICC: All Zones Show 26V Simultaneously—No Water Flow

Hunter ICC 12-zone: all zones read 26V when any one activated. 4 valve boxes found. No master valve wire. Disconnected all but one zone—still no water. Meter shows flow with system "on" but no visible output.

Diagnosis

Controller output stage failed — all stations hot simultaneously. Explains no pressure (all valves trying to open).

Isolation Tests

  1. Disconnecting other zones was correct — common wire must stay connected
  2. Test voltage at solenoid with single zone wire — should be 22-26VAC
  3. Manual bleed test: open valve bleed screw — if water flows, supply good
  4. Valve actuator tool: applies 24V directly to solenoid — tests valve independently
  5. Direct controller-to-solenoid test: run wires from controller terminals to solenoid

Three Failure Categories

  • Common wire cut
  • Controller failed
  • Water not reaching valves

Systematic voltage testing at each point isolates the fault.

Copyright © www.100flowers.win Botanic Garden All Rights Reserved