If two zones won't activate after you've re-stripped wires, replaced solenoids and valves, and swapped wires at the controller — the issue is likely insufficient voltage at the valve or a water supply issue.
Solenoids need ≥24 VAC to open reliably. Measure at the valve wires with zone active:
With zone active, slightly open the valve's bleed screw. Water should spray out — confirms valve is opening and water is flowing. If not, check for downstream blockage (crushed pipe, root intrusion).
Inspect the valve diaphragm and seat for debris. Even new valves can ship with manufacturing residue.
Richdel 446 PRi Controller No Zones Activate: Common Wire and Flow Stem Checks
Richdel 446PR Zone 2 Not Working—Solenoid Location and Replacement
Hunter XC Station 1 Won't Activate from Controller—Valve Works Manually