Toro Zone 1 Stays On All Cycle—Controller or Diaphragm

Toro system: Zone 1 runs entire cycle duration. Solenoid replaced, wiring checked. No fix.

Isolation Test

  1. Run Zone 2 (or any other)
  2. Measure voltage at controller Zone 1 terminal (red lead) vs COM (black)
  3. If voltage present → controller short → replace controller
  4. If 0V → valve mechanically stuck → rebuild/replace valve

Resource

Valve rebuild guide: irrigationtutorials.com