When a Toro EL-6+ activates two zones simultaneously and ignores others, the fault lies either in the controller or the field wiring. A voltage test at the controller’s terminal strip isolates the problem.
If the controller passes all tests, the issue is in the field wiring or valve solenoids. Inspect for crossed wires, damaged insulation, or faulty solenoids.
Toro ECTRA "Fuse" Flash on Zone 2: Internal Breaker Tripped by Shorted Solenoid or Wire
Toro Vision II Controller Repeatedly Cycles and Won’t Shut Off
Toro 212 Greenskeeper Won't Turn Off—Controller Wear
Toro GreensKeeper 212 'Power Off' Error Indicates Controller Failure
Toro EL-6A Controller Replacement Leads to Total Failure – Pro Diagnosis Needed
Toro Vision I F2 Fuse Blows Instantly – Transformer or Controller
Toro TMC-212 Odd/Even Watering Fails: Microprocessor Failure or Day Exclusion Error
Toro TMC-212 LCD Partial Display: Power Cycle or Replace
Toro DDC Pump Stays On After Cycle: Unused Zones Have Run Times Programmed
Toro TMC‑212 Manual Start Fails – Rain Drop Icon Not Flashing
Toro DDC-6: Blank Screen with AC Power, Works on Battery Only
Toro Vision Controller Mystery 1 AM Cycle: Default Program After Power Loss
Toro Vision Series I Blows Fuses After Storm: Replace Controller
Copyright © www.100flowers.win Botanic Garden All Rights Reserved