Toro Vision II controller: one zone reads 24V constantly (on or off), suggesting valve always open, but that zone doesn't water. System holds air pressure (winterizing), confirming valve is stuck CLOSED.
The controller terminal shows 24V, but that doesn't guarantee the solenoid receives it. Wire damage, corrosion, or a bad splice can allow voltage reading at the controller (open-circuit measurement) while preventing actual current flow to the solenoid.
The controller output driver for this station is likely failed in the ON state (leaking voltage). But if the wire is broken, the solenoid never actuates. The constant 24V reading is the controller's failed output transistor leaking, not a true signal.
Hunter ICC: All Zones Show 26V Simultaneously—No Water Flow
Sprinkler Solenoid Testing After Controller Voltage Confirmed—Ohmmeter Method
Hardie Rain Dial (~15 Years) Only Runs Zone A – Controller Failed
Hardie Total Control "Short" Error – Controller or Solenoid #6
SlimDial Timer: Zone Stays On After Off – Valve or Controller?
Toro Greenskeeper: One Zone Stays On Continuously
Rain Bird ESP-LX: Station 1 Sticks On, Manual Override Fails
Rain Bird ESP-8LXi+ Zone 1 Valve Stays Open: Controller or Wiring Fault?
Richdel 500 PRI Display Shows On But No Sprinklers: Test Controller Voltage Output
Toro Vision II Controller Repeatedly Cycles and Won’t Shut Off
Replacing Toro Hydraulic Controller: Conversion Kit or Electric Valve Upgrade
Converting a Toro Hydraulic Controller to Electric
Orbit 57020 Valve Zone 3 Won't Open Without Manual Bleed Adjustment
All Six Toro Valves Stuck Open After Winter: Pressure and Sequence Fix