K-Rain 1522 Pump Start Relay Not Engaging Pump

Newly installed K-Rain 1522 pump start relay fails to activate the irrigation pump.

Voltage Verification Steps

  1. Controller output: Measure 24VAC at controller's MV/Pump Start terminal when zone runs
  2. Relay input: Measure 24VAC at relay's control terminals

Diagnosis

  • 24V at controller, none at relay: Broken/loose wire between controller and relay
  • 24V at relay but pump doesn't start: Relay coil failure, contactor issue, or pump power problem
  • No 24V at controller: Controller output failure or programming issue

Most common: wire damage during installation or loose terminal connections. Check entire low-voltage run from controller to relay.