The controller display works (shows time), but manual zone activation fails. Slide switch to RUN, select station, set 3 minutes, press MANUAL - nothing happens. Worked this morning.
Remove the 9V battery. If the display goes blank, no AC power is reaching the controller. Check transformer, outlet, GFCI, and circuit breaker.
Main irrigation shutoff valve must be open. Check any master valve or backflow preventer valves.
With multimeter on VAC, measure between active station terminal and Common (C) while manually running that zone. Need 22-26 VAC. If absent, controller is faulty.
Problem is in field wiring, solenoid, or valve diaphragm. Test voltage at the valve solenoid wires.
Since it worked this morning, check for recent changes: tripped GFCI, turned-off water valve, or physical damage to wiring from yard work.