Hardie Irrigation: Display OK but Valves Don't Respond

Symptom: Controller Shows Normal, No Valve Activation

Hardie unit worked fine, now display is OK but valves don't run (manual or auto).

Troubleshooting Sequence

  1. Check all wiring at controller and valve boxes. Ensure common wire is solid to all valves.
  2. Reset controller: Disconnect AC power and battery 5 min; restore and reprogram.
  3. Test controller output: AC voltmeter (24V scale), black lead to Common, red to Station 1 while running Station 1. Should read 22–26 VAC.
  4. No voltage: Replace controller.
  5. Voltage present: Field wiring fault (cut, short, corrosion).

Common Failure Points

  • Wire nuts in valve boxes corroded.
  • Common wire nicked during landscaping.
  • Controller output triac failed (common after surges).