Rain Bird ESP-8Si: PR OFF Fixed, But System Still Won't Run - Check Master Valve

ESP-8Si showed PR OFF, replaced fuse/battery, display normal, reprogrammed. System won't run: manual shows countdown but no water. Advanced through all zones, no luck.

Troubleshooting Checklist

  1. Water source on? Main valve, backflow preventer valves open?
  2. Master valve? If wire on MV terminal, master valve must open first
  3. Master valve solenoid? If master valve solenoid failed, NO zones get water
  4. Start times, run times, days set? Verify all three for each zone

Testing Master Valve

At controller: Multimeter on OHMS, red lead on MV terminal, black on C (Common). Reading should be 20-60 ohms. Outside range = bad solenoid.

At master valve (above ground, looks like anti-siphon valve): Same test on solenoid wires.

PR OFF History Significance

Original PR OFF (fuse blow) was likely caused by this same master valve solenoid shorting. Replacing fuse without fixing the short just delays the next blow.