Nelson EZ Pro 8306 shows "P" code intermittently on different zones at different times. Works sometimes, fails others.

Manual's Three Causes for "P" Code

  1. Wiring issues - Disconnected, shorted, or damaged wires/solenoids
  2. Too many solenoids per zone - Only ONE solenoid allowed per zone terminal
  3. Lightning damage - Controller damaged but intermittently functional

Troubleshooting Priority

  1. Check all wiring connections - At controller and every valve box. Look for corrosion, loose wire nuts, damaged insulation
  2. Verify one solenoid per zone - No daisy-chaining multiple valves on one terminal
  3. Test solenoids - Resistance should be 20-60 ohms each
  4. If all wiring/solenoids good → Controller likely has lightning damage

Why Intermittent?

Temperature changes expand/contract wires, making marginal connections work sometimes. Moisture affects corroded splices. Lightning-damaged controllers often work until thermal stress triggers failure.