After a plumber serviced your hot water heater, your 30-year-old sprinkler system stopped working—even manually—and displays codes like 1A06 and 5A02. Don't panic; this is a common issue with a straightforward fix.
The codes 1A06 and 5A02 aren't error messages at all. They simply indicate Station 1 on Program A set for 6 minutes and Station 5 on Program A set for 2 minutes. Your controller is functioning normally; the problem lies elsewhere.
Before diving into electrical tests, verify the plumber didn't shut off the main water supply valve to the irrigation system and forget to turn it back on. This happens more often than you'd think.
If the water is on, test the controller's voltage output to confirm it's sending power to the valves:
If you get 22–26 VAC, the controller is fine—the issue is in the valve or wiring. If voltage is low or absent, the controller needs replacement.
If replacement is necessary, the Irritrol Rain Dial series is a reliable, easy-to-program choice that professionals trust. It's a direct upgrade for older systems and offers long-term durability.
Start with the main valve check—it's the most likely culprit and the easiest to fix. Good luck!
Rain Bird RC-7Bi Overshoots Run Time: Timing Motor or Micro Switch Issue
Water Master 57161: Valve Turns On Briefly Then Repeats Every Minute
Hardie Rain Dial 9‑Station Display Reverts to PM – Microprocessor Failing
Hunter XC Station 1 Won't Activate from Controller—Valve Works Manually
Nelson/Hunter Controllers: Can't Program Stations 5 & 6
Toro Vision II Plus: Station Run Time Dial Spins Without Effect
Rain Dial 6/9/12 Station Controller Dead After 10 Years: Reset or Replace
Irritrol RD-600 Only Outputs 15VAC: Controller or Wiring Fault?
Rain Bird 600: Manual Mode Zone 2 Opens Zone 1 Instead
Hunter EC Controller Stations 1&2 Not Working: Power Surge Damage
Rain Bird MSC-SAT-24: Single Zone Not Activating
Adding Manual Pump Switch to Hunter Controller Without Feedback Damage
Testing a Rain Bird ESP-6TM Controller After Lightning Damage
Hunter Controller Fuse Blows on Station 5 – Find Bad Solenoid
Copyright © www.100flowers.win Botanic Garden All Rights Reserved