Rain Jet RJC-66 Flashing "1C/2C" Error—Relay and Wiring Check

Rain Jet RJC-66 shows flashing "1C" (station 1) and "2C" (station 2) in manual mode. Pump power supply checks good.

Troubleshooting Sequence

  1. Pump relay: Could be shorting controller output
  2. Relay-controller wires: Check for cuts/damage
  3. Controller-valve wires: Inspect for damage
  4. Valve solenoids: Test each (20-60 Ohms) — faulty ones short controller

Priority Order

Start with pump relay (high current device, common failure). Then field wiring. Then solenoids. "C" likely indicates "current" or "circuit" fault.