Hardie RD-1200 Controller Not Activating Stations: Voltage and Wiring Test Procedure

12-station Hardie RD-1200 (~11-12 years old) shows programmed but no stations run. Manual button does nothing.

Standard Diagnostic Sequence

  1. Verify water supply on.
  2. Check controller output: 24 VAC at COM and zone terminal when zone activated manually.
  3. If voltage good (24-27 VAC), ohm-test field wiring continuity (solenoid ~30 ohms; 6-8 = short).
  4. Disconnect at valve to isolate solenoid vs. wire short.
  5. Check wire resistance alone (few ohms).

Tony provides the full multimeter procedure for both voltage and resistance testing. This is the universal troubleshooting path for "controller shows on but valves don't open."