After replacing four leaking backyard valves, the system works manually but from the timer, Zone 2 starts whenever any other zone runs (losing pressure but staying on). The controller is an older Nelson with a "P" terminal but no apparent master valve.
The "P" terminal powers a pump start relay or master valve whenever any zone activates. If a zone valve is incorrectly wired there, it will run with every cycle. Systematic testing identifies the root cause without guesswork.
Hunter XC Controller Stuck on “OFF” – Rain Sensor Bypass
Toro Zone 3 Failure: Controller Voltage Test After Valve and Pump Replacement
Hydrotek 6000 Valve Won't Cycle to Next Zone
Every Other Zone Pairs Running Together: Controller or Field Wire Cross
Manual Sprinkler Valve Won't Shut Off: Ball or Gate Valve Failure
Zone 6 Works Manually But Not from Controller: Electrical Fault
Nelson Controller: Zone 2 Runs With Every Other Zone — Wiring or Valve Issue?
Sprinkler Head Runs Non-Stop? The Valve Diaphragm Is Stuck Open
Troubleshooting a “Possessed” Zone Valve That Runs With Every Station
Troubleshooting a Sprinkler Zone That Shows Active but Delivers No Water
RC-7BI Controller Single Zone Operation: Stuck Valve Diagnosis
Copyright © www.100flowers.win Botanic Garden All Rights Reserved