1. Home
  2. Question and Answer
  3. Houseplants
  4. Garden Articles
  5. Most Popular Plants
  6. Plant Nutrition

14 Heads on One Zone: Pressure Drop Proves Too Many Heads

Hunter system installed Oct. Zone with 14 heads (2x 360°, 12x 180°) won't pop up. Contractor says replace pressure valve. User has 60 PSI static. Asks if 14 heads too many or valve issue.

Pressure Test Results

User tested each zone:

  • Zone 1 (14 heads): 60 → 20 PSI
  • Zone 2 (5 heads): 60 → 50 PSI
  • Zone 3 (7 heads): 60 → 50 PSI
  • Zone 4 (9 stream heads): 60 → 55 PSI
Zone 3 + faucet: 60 → 30 PSI.

Diagnosis: Friction Loss / Too Many Heads

Matt: "What you are seeing with the pressure drop for each zone is 'friction loss'... Zone one has too many heads on it. Your contractor assumed or didn't care to check the water so you have a problem zone."

Fixes

  1. Split zone into 2 (new valve, maybe larger controller).
  2. Reduce nozzle sizes: #5 for part-circles, #7 for 360s, #3-4 for corners. Target 35-40 PSI running.

Contractor responsible for flow-testing design. Nozzle change is cheapest fix.

Copyright © www.100flowers.win Botanic Garden All Rights Reserved