4-zone system: 2 front zones low pressure (2 years worsening). Side/back fine. Supply fully open. Valve replaced—no change. No visible leaks. Capped heads test—no wet soil.
Bad leak would show surface water. More likely: pipe restriction (crushed, root intrusion, debris) or valve not opening fully.
Measure at meter to quantify the problem.
Water Running Sound at One Valve When System Off – Valve Not Sealing
Rain Bird ESP-LX "Fault 4" Code: Zone Skipped
Single Zone Pressure Drop on Hardie Controller System
Hydrotek 4000 Low Pressure Daytime—K-Rain Timer Solenoid or Supply
Hunter SRV Valve Won't Shut Off: Flush, Replace Diaphragm, or Swap Valve Internals
Choosing a Sprinkler Valve for Low-Pressure Tank Drainage
One Zone Lost Pressure: Hardie Valve Diaphragm Likely Culprit
Sprinkler Solenoid Testing After Controller Voltage Confirmed—Ohmmeter Method
Why a Sprinkler Head Leaks When the System Is Off: Diaphragm Wear
Sprinkler and Drip System Not Activating: Master Valve or Main Supply Issue
Troubleshooting a Stuck Irrigation Zone: Why Zone 19 Won't Shut Off
Muriatic Acid in Sprinkler Well – Not Recommended
Control Valve Won't Shut Off – Replace Valve After Diaphragm Fails
Copyright © www.100flowers.win Botanic Garden All Rights Reserved