You cannot directly switch a 220V pump with a 120V timer. The timer's low-voltage output (24 VAC) can only control a pump start relay, which then switches the 220V pump circuit.
Some mechanical timers (e.g., Intermatic, Hydrotek) have line-voltage switching contacts rated for 1.5 HP. If yours does, you can wire the pump directly to the timer's load terminals — but verify nameplate ratings first.Electronic Timer? Must Use Relay
Electronic timers (Hunter, Rain Bird, Irritrol) only output 24 VAC — always require a pump start relay for 220V pumps.
Provide timer model and pump specs (HP, voltage, phase) for exact relay recommendation.