Orbit Timer Pump Start Fails: Voltage Drops Under Load, Controller or Wiring Fault

24V at Pump Terminal No Load, Drops to 1V with Relay Connected

Relay tested OK. Other terminals work. Pump terminal fails under load.

Diagnosis

Check voltage at relay end of wires. If 24V there → relay fault. If 1V → wire fault. But user says other terminals work, even driving relay from station terminal.

Conclusion

Orbit controller pump terminal output stage failed. Orbit not repairable. Replace with Irritrol Rain Dial or Rain Bird ESP — quality, repairable.