Imperial Valet Timer: 19 V on All Zone Terminals Constantly

Timer won’t run programs; 19 V on zones 1‑4 regardless of selection. Zones 5‑6 unused, no voltage.

Test

  1. Disconnect all field wires (1‑4 and C).
  2. Set to auto, put pin for today, advance to zone 1.
  3. Measure voltage at terminal 1 vs C (should be 22‑26 VAC).
  4. Move lead to terminal 2 – if voltage still present, controller has internal short.
  5. If only terminal 1 shows voltage, field wires are crossed.
  6. If voltage only 19 VAC with wires disconnected, replace transformer.