New home, sprinklers work via manual bleed but not through Rain Bird controller. Controller zones read 26V. At solenoid wire ends: only 2V.
Was the solenoid CONNECTED or DISCONNECTED when you measured 2V?
2V = Bad wire. High resistance break (partial cut, corrosion, bad splice) allows tiny leakage current but can't deliver solenoid operating current. You must find and repair the break, or run new wire.
2V under load could mean:
But open-circuit 2V is definitive: the wire is damaged.