Two KD6 controllers (front/back yard). Back works; front won't activate any zone. Display works, dial functions, but manual start does nothing for any zone.
Insert small flat screwdriver into reset contacts (usually two small pins/holes on circuit board). Display blinks, controller returns to default program.
Test controller output voltage (22-26 VAC at zone terminal vs Common). If no voltage with wires disconnected → controller failed. If voltage present → wiring or valve issue.
Since back controller works on same property, compare settings and wiring between the two units.