Hunter SRC Plus works with water but 1972 Hardie/Buckner valves won't open for compressed air winterization (80 PSI). 28V at controller, 20 Ohm solenoids.
Diaphragms hardened with age. Water pressure (40-60 PSI) lifts them; air (80 PSI) lacks sustained pressure to overcome stiff diaphragms.
Replace diaphragms on all 3 valves. 42-year-old rubber is brittle.