The controller displays "PR off" (power off) and has blown through five 1-amp fuses in quick succession. Each replacement fuse fails immediately upon power-up.
"PR off" indicates the controller has no power due to the blown fuse. The system is protecting itself from a short circuit somewhere in the output circuit.
Use a 1.0 amp, 250-volt fast-blow fuse - which you're already doing correctly. The problem isn't the fuse rating; it's a genuine short circuit.
Systematically test each zone to identify which valve or wiring run causes the short:
Once identified, replace the faulty solenoid or repair the damaged wiring section.
New Rain Bird System Shows "5 NOMOD": Module Not Seated
Mystery Middle Valve: Leaking, No Visible Output - What Is It For?
Rain Bird PC-106PS: Dog Chewed Wires, Need Reconnection Guide