Irritrol RD-900 Loses Programming: Power Supply Suspect

Two RD-900 units (one new exchange) revert to factory defaults (10 min/station) every few days. Battery tests good; programming holds on battery alone during power loss.

Key Question

Does the time of day also reset, or only the run times? If the clock resets too, the AC power supply or its regulation circuit is likely failing, causing the controller to behave as if power cycled.

Next Steps

  • Verify transformer output (should be ~24 VAC under load).
  • Check for loose AC connections or a failing outlet.
  • If power is stable and only run times reset, the controller’s non-volatile memory may be defective—replace the unit.

Given the age of the RD-900 design, a new controller (Rain Dial-R, Hunter, or Rain Bird) is more reliable than repairing vintage electronics.