Your Hunter Pro-C system has a master valve. Station 1 runs continuously whenever Stations 2–5 operate, but works fine alone. You've replaced a solenoid, cleaned valves, checked wiring—no fix. The issue: Station 1's valve is stuck open, and the master valve pressurizes the mainline whenever any zone runs.
Once identified, replace both the diaphragm and solenoid on that valve. A torn diaphragm or stuck solenoid plunger causes constant seepage that becomes full flow when the master valve pressurizes the line.
Replacing the wrong solenoid, cleaning the wrong valve, or checking wiring won't help if the faulty valve isn't the one you serviced. The master valve setup masks the problem until you isolate the correct valve.
Follow the Station 6 pressurization method—it's the definitive way to map valves to stations on master valve systems. Good luck!
Rain Bird ESP-8LXi+ Zone 1 Valve Stays Open: Controller or Wiring Fault?
Richdel Valve Thumping and Air in Lines: Diaphragm or Solenoid Port Issue
Imperial 11‑Station Timer Trips Reset – Master Valve Solenoid or Other Zone?
All Zones Come On Simultaneously – Stuck Solenoids or Valve Debris
Hunter XC Station 1 Won't Activate from Controller—Valve Works Manually
Nelson EZ Jr Controller: All Valves Pulse On Then One Stays On – Wiring Error
Zone Works Manually But Not Electrically: Valve Opening Issue
Locating a Shorted Solenoid on Hardie Total Control 12-Station System
Sprinkler Zone Won't Run Automatically – Valve Port or Diaphragm Issue
Hardie System Zone 1 Stays On – Need Model and Shutoff Method
Toro Vision 1 System Requires Manual Bleeding of Master Valve
Toro Vision 1 Zone Stays On – Valve Issue, Replace Solenoid/Diaphragm
Low Pressure on One Station of Six
Toro Vision II Plus: Station Run Time Dial Spins Without Effect
Copyright © www.100flowers.win Botanic Garden All Rights Reserved