When zone 1 is triggered (manually or automatically), zone 2 also runs. Three possible causes, tested in order:
Disconnect zone 2 wire at controller. Run zone 1. If zone 2 stays off, controller has internal short—replace controller.
Reconnect at controller, disconnect zone 2 wire at valve. Run zone 1. If zone 2 stays off, zone 1 and 2 wires are touching underground. Locate and repair the short.
Manually open zone 1 valve (turn solenoid CCW 1/4 turn). If zone 2 activates, zone 1 valve has a ruptured diaphragm allowing water into zone 2 line. Replace zone 1 valve.
Start at the controller—it's easiest. Work outward. Most common cause: controller failure.