Rain Jet Timer Skips Zone 5: Wire Swap Test to Isolate Controller or Valve Fault

6‑Zone Rain Jet Timer Stops After Zone 3; Zone 5 Never Runs

Swap the field wires at the controller:

  1. Remove zone 5 wire from terminal 5 and zone 1 wire from terminal 1.
  2. Connect the zone 5 wire to terminal 1.
  3. Run zone 1 manually.
  4. If zone 5 activates → controller terminal 5 is bad.
  5. If zone 5 still doesn’t run → valve 5 or its wiring is faulty.