Irritrol RD-600 "FU" Flashing Display—Fuse/Short Detection

RD-600 displays flashing "FU" (likely "FUS" + zone number missing). Indicates controller detected short on a valve circuit.

If Display Damaged (Missing Zone Number)

  1. Replace solenoid on valve #1, test
  2. If persists, move to valve #2, etc.
  3. Use same new solenoid for testing

Better: Multimeter Test at Controller

  1. Set multimeter to 200 Ohms
  2. Black lead on COM (white wire)
  3. Red lead on each zone terminal
  4. Reading <20 Ohms = short on that zone
  5. Replace that zone's solenoid

Also Check

Field wiring for shorts (nicked insulation, water in splice). Repair with waterproof connectors.