A homeowner converted to low-flow sprinklers requiring longer run times. Wants to run 3 solenoids simultaneously but gets voltage error. Asks about using relays.
Most residential controllers (24VAC transformers) support only 2 solenoids simultaneously. Running 3+ drops voltage below operating threshold, triggering error. This is a transformer capacity limit, not a wiring issue.
Adding relays doesn't increase transformer capacity. The 24VAC transformer still must power all activated solenoids. Relays add their own coil load, worsening the problem.
Schedule zones sequentially. Modern controllers stack start times automatically to avoid transformer overload. Low-flow zones need longer runs, not simultaneous operation.
Toro TMC-212 Hydraulic System: Diagnosing a Stuck-On Zone
Toro Vision II Plus Runs Every Cycle Twice: Seasonal Adjust or Extra Start Time
Toro DDC Runs at 1 AM and 6 AM: Extra Start Time in Program A, B, or C
Irrigation Pump Runs But No Water at Valves—Master Valve or Pump Relay
Setting Different Run Times for Multiple Start Times on Hardie Touch Command XL
Hardie HR-6100 All Zones Run on Water Turn-On: Valve Bleed Screws Left Open
Irrigation Scheduling: Frequent Light vs. Infrequent Deep Watering
Utilitech 2 HP Irrigation Pump Hums but Won’t Run – Motor or Electrical Issue?
Lightning Strike on Irrigation System: Testing Controller & Valves
Hardie RD900 Clock Flips AM/PM Daily – Microprocessor Failing
Hardie System Zone 1 Stays On – Need Model and Shutoff Method
Orbit Valve Box Full of Water – Leak or Groundwater?
Toro Vision II Plus: Station Run Time Dial Spins Without Effect
Designing a Home Irrigation System: Materials, Components, and Best Practices
Copyright © www.100flowers.win Botanic Garden All Rights Reserved