Hunter Pro‑C: Zones 1 and 7 Always On – Module Damaged

After storm, new panel installed. Zones 1 and 7 run constantly, low pressure. Clicking in zone 1‑3 valve box.

Diagnosis

Controller sending power to multiple valves simultaneously. Measure voltage at each port (black on C, red on zone). If multiple zones show voltage at once, module damaged. Clicking is solenoid activation.