1. Home
  2. Question and Answer
  3. Houseplants
  4. Garden Articles
  5. Most Popular Plants
  6. Plant Nutrition

toro ecxtra controler


Question
just recently zones 2,3,4,6 have stopped running.  Ive tried to manually get them going, even reprogrammed in "B" and still not functioning.  Need troubleshooting help.  thanks

Answer
First question: Has there been any work done on the property that could have cut any of the control wires that run from the controller to the valves?

If you have a volt and ohm meter please start at the terminals of the controller and check the how many volts are being sent when those stations in question when they are turned on.

Also if you have a pump for those in question make sure that is part of the program as well.

Check the ohms on the station wires in question to see if they are any open circuits.

Check the solenoids to make sure they are not damaged.

If you do not have any tools for troubleshooting try the following:

Take one station wire that you know works and switch it to a terminal of a zone that is not working> this will tell you if the controller is sending out the correct voltage on a terminal in question.

Also you can take a wire from a station that is not working and try it on a terminal that you know is working. If the station still does not work then you will have to troubleshoot the wire from the controller to the valve and to ensure that the solenoid is not damaged. Solenoids do go bad. I replaced 3 at one house today where 3 zones stopped working. I assume that the house experienced a power surge.  

Copyright © www.100flowers.win Botanic Garden All Rights Reserved