Testing a Rain Bird Controller Transformer After a Power Surge

Rain Bird Controller Blank After Power Surge—Transformer or Controller?

A power surge can knock out the controller’s transformer or the controller itself. A simple voltage test distinguishes the two.

Measure Transformer Output

  1. Open the controller cabinet and locate the two wires labeled 24VAC on the terminal strip.
  2. With a multimeter set to AC volts, measure across these two wires.
  3. 24 VAC present: Transformer is good; the controller’s microprocessor is likely damaged.
  4. No voltage: Transformer has failed—replace it (input 120 VAC, output 24 VAC).

Also check for a blown fuse on the controller board (some models have one).