New Orbit anti‑siphon valve leaks from the vent. Highest head is 10 ft above valve. Owner asks if a check valve at the bottom allows omitting the anti‑siphon.
Code requires anti‑siphon valves 18 in above the highest head. The leak is likely due to insufficient pressure to seat the vent poppet. Since the installation isn’t to code and a check valve exists, replace it with an inline valve (no anti‑siphon).